Combined loop and RCD testers
View Large
Product Name : Combined loop and RCD testers
Product Origin : Hong Kong S.A.R., China
Product Category : Megger
More Products : Click here!
Contact Details : 運揚有限公司 WANCO LIMITED
Product Code : LRCD220
Product Details

 Combined loop and RCD testers



環路及電阻器電容器


Model : LRCD220

 

THe Megger LRCD220 with the addition of 2 wire fast testing, plus phase to phase and phase to earth measurement. This instruments will not trip RCDs rated at 30 mA or greater during loop testing, even electronic RCDs.

 

* Specification

 

Voltage measurement:

(LRCD220):

0 V - 500 V

Accuracy:

±2% ±2 digits




Frequency measurement:

(LRCD220)

Range:

25Hz to 450Hz

Accuracy:

25.0Hz to 199.9Hz ±0.1Hz

200Hz to 450Hz ±1Hz

Phase rotation indicator

(LRCD220 only)

Three wire identification of phase rotation.

Frequency:

45Hz to 65Hz

Loop testing:

Loop ranges (to EN 61557-3)




No Trip Loop test 3-wire (Line to Earth) (LRCD220)

Supply:

LRCD220 100V - 280 V 45Hz to 65Hz

Nominal test current:

15 mA

Loop Accuracy:

0.01 Ω - 9.99 Ω (±5% ±0.03 Ω)

10.0 Ω - 99.9 Ω (±5% ±0.5 Ω)

100 Ω - 999 Ω (±5% ±5 Ω)

1.00 kΩ - 2.00 kΩ (±5% ±30 Ω)




HI current Line/Earth loop test 2 wire (LRCD220 only)

Supply:

100 V - 480 V

Nominal Test Current:

15 mA to 2.4 A

Loop accuracy:

0.01Ω - 9.99 Ω (±5% ±0.03 Ω)

10.0Ω - 99.9 Ω (±5% ±0.5 Ω)

100Ω - 999 Ω (±5% ±5 Ω)

1.0 kΩ - 2.00 kΩ (±5% ±30 Ω)

Line/Line (LRCD220 only)

Supply:

100 V - 480 V 45Hz to 65Hz




Prospective Fault Current (PSCC)

Prospective fault current = Nominal supply voltage/Loop

resistance

Accuracy is derived from loop test

1 A - 199 A 1 A resolution

0.20 kA - 1.99 kA 10 A resolution

2.0 kA - 19.9 kA 100 A resolution




RCD Testing

RCD Test Ranges (to EN61557-6)

LRCD220 10mA, 30mA,100mA, 300mA, 500mA, 1000mA

Supply voltage:

LRCD220 = 100 V - 280 V 45Hz to 65Hz

Test Current Accuracy:

No Trip Test:

(1/2I) –8% to –2%

Trip Test:

(I, 5I) +2% to +8%

Trip Time:

±1% ±1ms

Fault (Touch) Voltage

Displayed range:

0 V to 50 V

Error:

+5%/+15% ±0.5 V

Temperature and humidity

Operating Range:

-5°C to +40°C

Operating Humidity:

93% R.H. at +40°C max.

Storage Range:

-25°C to +70°C

Maximum altitude:

2000m

Environmental Protection:

IP54

Safety

IEC 61010

Meets the requirements of IEC61010-1 Cat III 300V phase to earth.




EN61557

Complies with the following parts of EN61557,Electrical safety in

low voltage systems up to 1000 V ac and 1500 V dc- Equipment for

testing, measuring or monitoring of protective measures:

Part1- General Requirements

Part3- Loop resistance

Part6- Residual current devices

Power supply

Battery: 8 x 1,5 V cells IEC LR6 type (AA alkaline).

Rechargeable: 8 x 1.2V NiCd or NiMH cells.

Battery Life: 2000 consecutive tests

Weight: All units 980gms

Dimensions: All units 203 x 148 x 78 mm

E.M.C.

In accordance with IEC61326-1